USER MANUAL FOR COMFLEX-6Q00 5W
ENU STATUS: 1-0-1 Copyright - refer to title page Page 62
6 ALARMS AND TROUBLESHOOTING
6.1 ALARMS
Table 14: MU Alarm List
Alarm List Alarm Condition
Over-Temperature
Alarm
Alarm when equipment temperature is higher than the threshold, otherwise
normal;
Alarm judgment period: 3 minutes by default;
Alarm threshold : 80 by default.
Optical Tx Alarm
Alarm when Optical Transmiting power is lower than the threshold, otherwise
normal;
Alarm judgment period: 3 minutes by default;
Alarm threshold: -7dBm by default.
Optical Rx Alarm
Alarm when Optical received power is lower than the threshold, otherwise
normal;
Alarm judgment period: 3 minutes by default;
Alarm threshold: -10dBm by default.
DL Input Power
Overload Alarm
Alarm when DL input power is higher than the threshold, otherwise normal;
Alarm judgment period: 3 minutes by default;
Alarm threshold: 32dBm by default.