Ambient temperature too high
Ventilate compressor room
Check electric motor and thermistor
Sensor, connections or lines defective
Check sensors, connections and lines
Cross section of the electric supply
lines too small
Measure power requirement,
if necessary, replace lines
Power requirement too high
Oil fine separator clogged,
replace, if necessary
Top up oil in the pressure reservoir
Oil injection pressure too low
Replace oil filter cartridge,
clean oil system
Excessive oil temperature
Check oil cooler and fan/
Check oil thermostat
Check cooling water circuit
(only for Lxx W – water-cooled units)
Excessive idling
pressure
Intake regulator does not close correctly
Check intake regulator
Check solenoid valves
Oil in the compressed air
Oil fine separator defective
Replace oil fine separator cartridge
Minimum pressure valve defective
Check minimum pressure valve
Orifice of oil extractor clogged
Intake regulator setback function
defective
Intake regulator does not close correctly
Check intake regulator
Check solenoid valves
Frequent emergency shutdown
The emergency shutdown may only be
activated in the case of safety-relevant
functional problems
Oil fine separator clogged and final
compression pressure sensor defective
Replace oil fine separator cartridge and
change final compression pressure
sensor
Intake regulator closes too slowly
Check intake regulator and solenoid
valves
Mains pressure sensor defective
Replace mains pressure sensor
Warning
Never operate the screw compressor with defective safety valve!