EasyManua.ls Logo

CONFLOW UNIWORLD Series - Automatic Commissioning; Manual Commissioning

CONFLOW UNIWORLD Series
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UNIWORLD Series M/UNIWORLD-M/E ed. 01 2020
WWW.CONFLOW.IT Page 21
3.12.1 AUTOMATIC COMMISSIONING
Only possible if at least one of the limitations (opening/closure) is set as the “torque” or “in the automatic position”.
Press the start button for 3 sec.
For the position of the start button see
1
During the commissioning phase (green light flashing, the valve is
moving in both the limit positions)
2
3
Fixed green light The valve has successfully started
and is ready to enter in operation
3.12.2 MANUAL COMMISSIONING
1
2
Connect the PSCS-USB cable to the PC and start the software
Select the type of actuator and the program interface
3
4
Select “Operate” Commissioning
and confirm with OK
During manual commissioning, ensure the correct value for the
closure position or binary input to control the valve in the closure
position based on the configuration established is permanently
applied.

Table of Contents