Salwico ST400 O2
Salwico GS5000
Calibration Instruction
Question and Answer IconNeed help?

Do you have a question about the Consilium Salwico ST400 O2 and is the answer not in the manual?

Consilium Salwico ST400 O2 Specifications

General IconGeneral
BrandConsilium
ModelSalwico ST400 O2
CategoryMeasuring Instruments
LanguageEnglish

Summary

Salwico ST400 O2 Calibration Instruction

Preliminaries

Introduces the ST400 O2 detector, its sensor type, lifespan, and replacement article.

Prerequisites for Calibration

Details menu navigation, selecting the detector, and disabling it before calibration can proceed.

Span Calibration Procedure

Explains how to connect a multi-meter and adjust the SPAN potentiometer to 17.4 mA using breathing air.

Zero Calibration Procedure

Outlines connecting a multi-meter and adjusting the ZERO potentiometer to 4.0 mA using a nitrogen gas bottle.

Reconnecting Disabled Detectors

Describes the steps to re-enable a detector from the disablements list within the Salwico GS5000 system.