1Calibration Instruction for Salwico ST400 O2 Calibration Instruction
2
5103029_Salwico ST400 O2_Calibration Instruction_I0_EN_2014_B
A Test points
B SPAN potentiometer
C ZERO potentiometer
1.2 Prerequisites
1 Use the arrow keys on the control panel to
manoeuvre through the different menus.
Press the right arrow key to access the
menu tree.
2 Scroll to 4 Gas Detectors and press
Continue.
3 Scroll to the detector that should be
calibrated and press Options.
4 Scroll to 3 Disable and choose Continue.
5 You have to confirm the disablement before
you can proceed.
Press Disable to continue.