INSTALLATION,
OPERATION
&
MAINTENANCE
MANUAL
SINGLE PACKAGED ROOF TOP AIR CONDITIONERS
'PT' SERIES
MODELS: PT036 - PT360
Part Number: 800-213-03

Questions and Answers

  • J
    Jason StewartAug 16, 2025
    Why is my Cooline PT036 Air Conditioner blower running, but with not enough supply air?
    • H
      hollyrodgersAug 16, 2025
      There are several reasons why your Cooline Air Conditioner might be running, but not providing enough air. The issue could be due to a loose belt (adjust it and check the belt tension), a variable pulley that is wide open (adjust the pitch of the pulley), or obstructions in the return air (check and remove any obstructions). Additionally, high static pressure (verify static pressure and fan performance data), an improper pulley selection (change the pulley if the blower motor ampere is within the rated load), closed dampers or improper air balance (check that all dampers are opened properly and balance the air), a dirty filter (clean it), or a dirty cooling coil (clean it) could be the cause.
  • C
    Christina AustinAug 19, 2025
    What to do if my Cooline PT036 compressor runs, but short cycles?
    • M
      Michael SuttonAug 19, 2025
      If the compressor in your Cooline Air Conditioner is running but short cycling, it could be due to a safety circuit opening because of low suction pressure, high discharge pressures, or an overload protector. You should verify the reason for low suction pressure and high discharge pressure. Also check the dome temperature and RLA for each phase and verify the reason. Additionally, check if the thermostat is in a cold location and relocate it if needed. Try lowering the temperature setting on the thermostat to 21 degrees Celsius for testing.
  • D
    Derrick LeeAug 22, 2025
    What causes low suction pressure in my Cooline Air Conditioner?
    • K
      Kimberly HallAug 22, 2025
      Low suction pressure in your Cooline Air Conditioner can be caused by several factors. These include having less Freon (check for gas leaks and charge Freon as needed), a loose belt (adjust it and check the belt tension), a variable pulley that is widely open (adjust the pulley), a dirty filter (clean it), or a dirty cooling coil (clean it). Other potential causes are restricted return air (check return air grille sizes against the design), an improperly installed or located expansion valve bulb (verify and correct it), or a restriction in the expansion valve or filter dryer (check and correct or replace it).
  • T
    theresasmithAug 25, 2025
    How to fix a Cooline PT036 thermostat with no display?
    • E
      Erin AllenAug 25, 2025
      If your Cooline Air Conditioner thermostat has no display, there are several things you can check: - First, ensure that the unit has power, switch ON the circuit breaker and replace the fuse if it is blown. - Second, check the field wiring against the diagram. - Third, check for loose connections and correct them. - Finally, the thermostat itself may be defective and need to be replaced.
  • R
    Robert BrownAug 27, 2025
    Why does my Cooline PT036 Air Conditioner blower run, but the compressor is not working?
    • M
      Matthew BriggsAug 27, 2025
      If the blower in your Cooline Air Conditioner is running but the compressor isn't working, it could be due to several reasons. The safety circuit might be open because of low suction pressure, high discharge pressure, or an overload protector (reset the unit and determine the reason; check high and low pressure). Other potential causes include a defective compressor contactor (replace it), burned wiring (check and replace it), or a defective compressor (replace it).
  • J
    Jennifer KaneAug 30, 2025
    Why is my Cooline PT036 discharge pressure high?
    • K
      Kenneth WilliamsAug 30, 2025
      High discharge pressure in your Cooline Air Conditioner can stem from several issues. The condenser fan motor might not be working properly (check if the fan blade is stuck and correct it). An excess of Freon charge (check Freon and adjust if necessary), a dirty condenser (clean it), high ambient conditions or obstructed air in the condenser (verify the reason and correct it), a defective fan motor capacitor (check and replace it), or a defective fan motor (check and replace it) could also be responsible.
  • M
    Michael SalazarSep 2, 2025
    Why is my Cooline PT036 blower not running and the compressor short cycles?
    • J
      Joshua JordanSep 2, 2025
      If the blower in your Cooline Air Conditioner is not running and the compressor is short cycling, it could be due to a few reasons. The blower belt might have slipped or is not fixed properly (correct the belt and check its tension and alignment). Other possible causes include faulty wiring (check the wiring against the diagram), burned wiring (check and correct it), a defective blower motor contactor (replace it), or a defective blower motor (replace it).
  • F
    frederick39Sep 4, 2025
    What causes high suction pressure in my Cooline PT036 Air Conditioner?
    • A
      Ariel EdwardsSep 5, 2025
      High suction pressure in your Cooline Air Conditioner can be caused by several factors: excess Freon charge (verify and adjust it), excess air quantity (adjust air quantity), high room temperature (check and verify, isolate the area to be cooled and observe), an undersized unit serving a large area (check design/unit selection), an expansion valve that is widely open (check superheat and adjust if required), or a defective compressor valve (check and replace the compressor).
  • T
    Thomas LunaSep 7, 2025
    Why is my Cooline PT036 Air Conditioner blower running and delivering excess air?
    • K
      kaitlinmyersSep 7, 2025
      If your Cooline Air Conditioner blower is running and delivering too much air, it could be because the variable pulley needs more tightening (adjust the pitch of the pulley). It could also be due to an improper pulley or motor selection (select a suitable combination) or low external static pressure (check the duct design).
  • H
    harold49Sep 10, 2025
    What to do if Cooline Air Conditioner thermostat shows a faulty indication?
    • R
      rrobinsonSep 10, 2025
      If your Cooline Air Conditioner thermostat shows a faulty indication, it could be due to a safety circuit opening because of a low-pressure switch, a high-pressure switch, or an overload protector. Verify the reason and correct it.

Summary

General Unit Information

General Safety Issues and Precautions

Details three degrees of safety hazards (WARNING, CAUTION, ATTENTION) and essential safety measures.

Installation Instructions

Service Clearance Requirements

Specifies required clearances around the unit for service access and proper air circulation.

Operation Instructions

Start-Up Inspection Checklist

Lists essential checks to perform before switching the unit on for initial operation after installation.

Electrical Data Specifications

Presents electrical specifications, including voltage, current ratings, and component data for all models.

Performex-1 Controller Operation

Details the features and operational capabilities of the Performex-1 electronic controller.

Maintenance Instructions

Troubleshooting Common Issues

Provides a chart to diagnose and resolve common unit symptoms, causes, and corrective measures.

Schematic Wiring Diagrams

Presents schematic wiring diagrams for various unit models, illustrating electrical components and connections.