Why is my Cooline PT036 Air Conditioner blower running, but with not enough supply air?
- HhollyrodgersAug 16, 2025
There are several reasons why your Cooline Air Conditioner might be running, but not providing enough air. The issue could be due to a loose belt (adjust it and check the belt tension), a variable pulley that is wide open (adjust the pitch of the pulley), or obstructions in the return air (check and remove any obstructions). Additionally, high static pressure (verify static pressure and fan performance data), an improper pulley selection (change the pulley if the blower motor ampere is within the rated load), closed dampers or improper air balance (check that all dampers are opened properly and balance the air), a dirty filter (clean it), or a dirty cooling coil (clean it) could be the cause.