i-on16 Programming
Page 57
Disabled.
The control unit does not monitor the telephone line.
Audible.
If the system is unset then the system logs the
event. The control unit produces a short audible tone
every minute. Entering a valid access code silences
the sounders and the display indicates a telephone
line fault. The system can be set again with the line
fault present.
If the system is set then the control unit logs the
event but does not give any tone or display. The
control unit cancels any programmed siren delay if
the line is out of order when an alarm occurs.
Note: Audible response is the NSI recommendation for
line fault.
Silent.
If the system is unset then the display indicates a
telephone line fault and the control unit logs the
event. The system may be set again with the line
fault present.
If the system is set then the control unit does not
give any indication or tone but does log the event.
The control unit cancels any programmed siren delay
if the line is out of order when an alarm occurs.