Page12
Referstoelectricdiagrams:
R1558..:Powerandsupplycircuit
R1998..:Wiring
R1057..:Powerlinefilter
S1110215:Selectorswitch,Manual,0,Automatic.
SälzerM220-61025-019M.20A.
K1111833:Relay,Finder60.13,11P,230V/50,10AAC1
M3110400:Motorforgear,230V/50,SaiaUFR40.230,
110430Capacitor0,22MYF
110410Gear,SaiaJ1M
M1111700:Mainairfan,230V,40W,ØstbergRFE140L
111622Capacitor4MYF
M2111702:Reg.-airfan,230V,41W,EBMG2E108-AA01-01,75C
111620:Capacitor1,5MF
E1111457:Electricheater,220-240V,1500W.-PTC-type.
HR15-15/22IS
E2111460:Electricheater,230V,10W
D1111850:Relayondelay(gearmotorandreg.airfan)
setfor1min.,SaiaKOL312H7MRVPNOO
P2110001:Amp.meter,230V,5/25A,DeifEQ48,
P1112003:Hourcounter,230V/50.Saia230V/50,48x48
ThePTCtypeelectricheaterisonlyfunctioningwhenair
flowsthrough.Thisisthereasonwhynothermostatsor
thermostaticswitchisinstalled,asthefunctionofthese
componentswillberegulationoftheenergyfortheelectric
heater.
Thedehumidifierispreparedforexternalregulationbya
humidistat.Thereforeterminalsforthisconnectionispla-
cedintotheconnectionboxplacedonthefrontplateof
thedehumidifier,nexttothedryairoutlet.Theterminals
is6&7.Intheconnectionboxtheterminalsforpower-
connectionisplacedtoo(L1,N,PE).
Theterminals6&7areshuntedatdelivery.Thisshuntis
toberemovedandtheterminalsforthehumidistatconnec-
ted.
Atoperatingwithconnectedhumidistat,theselectorswitch
shouldbeinposition"automatic".
Thehumidistatshouldbeapprovedfor3A.
7.4ELECTRICCOMPONENTS,CR100.
THEINSTALLEDELECTRICHEATER:
WARNING:DONOTTOUCHTHEELECTRICHEATERWHENSWITCHED
ON,ASITISANUNINSULATEDLIVEWIRE.
7.5REGULATIONBYHUMIDISTAT.