Page13
ThedehumidifierCR100isconnected230V,1N+PE.Thedehumi-
difierissuppliedwitha2mcableforthepowersupply.
Powerconsumptionis1,0KW,externalfuses10A.
Thiscableisconnectedtotheinternalterminalsplacedin
thecompartmentunderthetopcover.
InthiscompartmentalsotheAmp.meter,hourcounter,selec-
torswitchandthepowerlinefilterareplaced.
Connectionofhumidistat,see7.5,above.
Theelectricheateris230V,1500Wandtheexternalinstal-
lationshouldbemadeforthis.
TheenergyconsumptionofthePTC-heaterisdependingofthe
airpassingthrough.
Atthenominalreg.-airflowof35m3/htheenergyconsump-
tionoftheheateris945W,(=indicationof4,1Aonthe
Amp.meter).Theairflowandtheenergyconsumptionisregula-
tedonthedamperdeliveredinourstandardreg.-ductsy-
stem(option).
NOTICE:theenergyconsumptionoftheelectricheaterinthe
firstsecondsisupto15A.
Thedehumidifiershouldbeinstalledindoors,placedona
wallbracketorsomeotherhorizontalbasis.Itshouldbe
placedonthefouroffrubbersupportsunderneaththeca-
binet.
8.1Themainairtobedriedisnormallytakenfromthe
room,andthroughthemainairfilterinthebackpla-
te.
Asstandardthedehumidifierisdeliveredwithfilter/
filterframe,butoptionalplatewithØ100connection
forinletaircanbesupplied.
Reg.-airinletshouldbefittedwithductØ80,andthe
build-infilter.
Reg.-airoutletshouldbefittedwithductØ80,instal-
leddrainingawayfromthedehumidifiertoallowthe
condensedwatertorunfree+damperØ80.
Ifthisisnotpossible,aholeØ4mmshouldbedrilled
underneathatthelowestpartoftheduct.
DryairoutletcanbeconnectedØ100mmducts.
Ingeneralductsofthesamesizeasplacedonthedehumidi-
fiershouldbeused-orbigger.
7.6ELECTRICCONNECTION.
SUBJECT:POWERCONSUMPTION&AIRFLOWS.
FREQUENTSTART/STOPONTHESELECTORSWITCHSHOULDBE
AVOIDED,ASITCANDAMAGETHECONTACTELEMENT,ORTHE
CONNECTEDHUMIDISTAT.
8.
CONNECTIONOFDUCTS:
INSTALLATION.