Page15
-thedryairflowcanbeadjustedwhenadamperØ100is
installedinthedryairduct.Ifonlyashortduct
isinstalled,theairflowshouldbereducedonthe
dampertoobtainthenominal100m3/h.
-thereg.-airflowcanbeadjustedonthedamperin
thereg.-airoutlet(option).Start-upwiththedamper
intheclosedposition,openinguntiltheAmp.meter
indicates4,1A(at230V).Checkthevalueagainafter
15min.ofoperation(onemoreadjustmentmightbe
necessary).
Reg.-airflowalwayshastobecontrolled.Checkthe
reg.-ductforallowingfreeblowingofthereg.-air.
Checkthatthereg.-airductisinstalleddrainingfrom
thedehumidifier.
Withtheelectricalsettingsandairflowsadjusted,the
dehumidifierwillthenoperateautomaticallybymeansof
theinternalcontrol-andsafetyfunctions-controlled
byanexternalhumidistat.
DehumidifierCR100onlyneedsaminimumofmaintenance.
Allcomponentsareservicefree,whichmeansnolubrication
oradjustment.
Onlythreethingsshouldbecheckedundernormaloperati-
on:
-airfiltersshouldbereplacedatleastevery2.month
-therotationoftherotorshouldbecheckedoncea
month.
-thepowerconsumptionoftheelectricheatershouldbe
checkedoften(reading4,1AontheAmp.meter).
Iftherotorrotatesduringoperation,andtheenergycon-
sumptionoftheelectricheatershowsapp.4,1A,youcabe
almostsurethatthedehumidifierisoperatingatanopti-
mum.
Weneverthelessrecommendsomeperiodicverificationof
theentiredehumidifier,toseeifallinternalfunctions
areokandcheckingofgasketsandmovingpartsforwear
andtear.
Thiswillensurethatthecapacityisonitsmaximum,and
thuswontwasteanyenergy.
11.1Ifthedehumidifierdoesnotstartwhenelectriccon-
nected,controltheexternalfuse.
HOWTOADJUSTTHEAIRFLOWS:
IMPORTANT:
10.MAINTENANCE.
11.TROUBLESHOOTING.