12 FnIO G-Series
Copyright(C)CREVIS Co.,Ltd Support +82-31-899-4599 URL: www.crevis.co.kr
- Aph Input acts as Encoder's A phase Input
- Bph Input acts as Encoder's B phase Input
B' 0010 (0x2)
Up
Up Counter
- Aph Input acts as Up Clock
- Bph Input is not used
B' 0011 (0x3)
Down
Down Counter
- Aph Input acts as Down Clock
- Bph Input is not used
B' 0100 (0x4)
Up Clock & Inhibit
Up Counter with Inhibit
- Aph Input acts as Up Clock Input
- Bph Input acts as Inhibit function for Up Clock Input
B' 0101 (0x5)
Up Clock & Reset
Up Counter with Reset
- Aph Input acts as Up Clock Input
- Bph Input acts as Reset function to Counter
B' 0110 ( 0x6 )
Down Clock & Inhibit
Down Counter with Inhibit
- Aph Input acts as Down Clock Input
- Bph Input acts as Inhibit function for Down Clock Input
B' 0111 ( 0x7 )
Down Clock & Reset
Down Counter with Reset
- Aph Input acts as Down Clock Input
- Bph Input acts as Reset function to Counter
B' 1000 ( 0x8 )
Up Clock & Down Clock
Up & Down Counter
- Aph Input acts as Up Clock Input
- Bph Input acts as Down Clock Input
B' 1001 ( 0x9 )
Clock & Direction
Up & Down with Direction
- Aph Input acts as Clock Input
- Bph Input acts as Direction Input ( Low = Up Count, High =
Down Count )
B' 1010 ( 0xA )
Encoder 4x (*1)
Encoder 4x
- Aph Input acts as Encoder's A phase Input
- Bph Input acts as Encoder's B phase Input
B' 1011 ( 0xB )
Encoder 2x (*1)
Encoder 2x
- Aph Input acts as Encoder's A phase Input
- Bph Input acts as Encoder's B phase Input
B' 1100 ( 0xC )
Frequency Measurement (*2)
1 sec Update
Simple Frequency Measurement, updated by 1sec, Hz Unit
- Aph Input acts as Frequency Input
- Bph Input is not used
B' 1101 ( 0xD )
Frequency Measurement
100 msec ( 0.1sec ) Update
Simple Frequency Measurement, updated by 100msec, Hz
Unit
- Available in case of Pulse Input >= 10Hz
- Aph Input acts as Frequency Input
- Bph Input is not used
B' 1110 ( 0xE )
Pulse Width Measurement
Simple Pulse Width Measurement, 0.1usec Unit
- Pulse Width(32bit), if 1234, then Pulse High(On) width is