121
Modbus Address of Display Data
12.
Modbus
Address
of
Display
Data
Description Notes
Range Unit MODBUS
Address
Operation frequency
0〜24000 0.01HZ 328
Current feedback
0〜9999
0.1A 329
Operation command
0〜24000
0.01HZ 330
DC voltage
0〜9999
0.1V 331
Output voltage
Vac=Output voltage / 2
0〜9999
0.1 332
External terminal
mode
0〜255
333
Module Temperature
112〜1130 0.1℃
234
Operation status
Bit2: 0=Stop, 1=RUN
Bit14: 0=FR, 1=RR
Operation command
MASTER changes:
Bit0: FWD command
Bit1: REV command
Clear Bit0 Bit1: Stop command
Bit2: Reset after failure
command
335
336
Failure
Bit 4,3,2,1,0 =
0:None
4:OCPA
5:OCPd
6:OCPn
8:OV
10:OH
12:OL
14:OC
15:PLU
16:OL2
17:BuOH
337
Power factor 0~100 0.01 338
Instant power 0~65535 0.01KW 339
KW-H 0~9999 0.01KW
H
340
MW-H 0~65535 0.1MWH 341
Current time of
multi-step function
0~999 1min 342
Yards counter’s low
8bits & Current step
of multi-step function
0~7 bit: Current step of
multi-step function
8~15 bit : Yards counter’s low
8bits
0〜16
1step
0〜255 0.01 yard
343
Yards counter’s high
16bits