Adjust and Function Specification
§Cd01 Setting procedure of frequency (Selective range 0-7)
The function cannot be modified during revolution.
Setting procedure of frequency is to select either panel key or external analog signal.
Cd01=0 Set frequency on operation panel, as the above items A-C.
Cd01=1 Set frequency by terminal In2 DC 0-10V/5KΩVR
Cd01=2 Set frequency by terminal In1 DC 4-20mA
Cd01=3 Set frequency by terminal In2+IN3 DC 0-10V/5KΩVR
Cd01=4 Setting from terminal In2, input DC0〜10V/VR 5KΩ hysteresis
Cd01=5 Setting from terminal In1, input DC4〜20mA hysteresis
Cd01=6 Setting from terminal In2+IN3, input DC0〜10V/VR 5KΩ hysteresis
Cd01=7 Set frequency by Multi-step function mode
§Cd02 Select Main monitor display (Selective range 0-15)
The monitor is consisted of four 7-segment LEDs, displays frequency, current and
various data by digital number and character.
Cd02=0 Display the frequency, LED HZ active
Cd02=1 Display the current, LED I active
Cd02=2 Display Ultimate speed, Hz and I LED de-active.
Cd02=3 Display DC voltage of DC BUS, showing d in front of value
Cd02=4 Display rms value of U.V.W. AC output,LED HZ, I active
Cd02=5 Display external control terminal status, showing E in front of value
Cd02=6 Display temperature rising of PIM module, showing b in front of value
Cd02=7 Display speed feedback. Check if MCK circuit working properly, then
the restart and free run start function (Cd28) will working normally.
Cd02=8 Display average speed of multi-step function (rpm)
Cd02=9 Display current step of multi-step function (step)
Cd02=10 Display current time of multi-step function (minutes)
Cd02=11 Display Yards counter value
Cd02=12 Display power factor (cos Θ)
Cd02=13 Display transient power (Kw)
Cd02=14 Display Kw-h
Cd02=15 Display Mw-h
§Cd03 Torque mode (Selective range 0,1)
The function cannot be modified during revolution.