Adjust and Function Specification
§ CE53 Multi-steps all files set to default (settable range 0~1)
The function cannot be modified during revolution
The setting can not be changed while the machine is working.
CE53=0 Data remain unchanged.
CE53=1 Reset data in files 1-6 to default.
§ CE54 Multi-steps memory duplicate function (settable range 1~6)
The function cannot be modified during revolution
The setting cannot be changed while the machine is working.
Duplicate current using file (CE05~CE46) to CE54 .
§ CE55 Yards counter clear (settable range 0~1)
Set CE55=1 to clear Yards counter.
§ CE61 Input terminal for Set Point and PI feedback (settable range 0~7)
The function cannot be modified during revolution
CE61 Target value PI feedback terminal
0 De-active PI control
1 Set by CE67 IN1
2 Set by CE67 IN2
3 Set by CE67 IN3
4 From terminal IN1 IN2
5 From terminal IN1 IN3
6 From terminal IN3 IN1
7 From terminal IN3 IN2
Note:
1. IN1(4~20mA) scale to 0~100.0 %, IN2、IN3(0~10V) scale to 0~100.0 %
2. output frequency = PI output frequency + set frequency
3. Make sure this parameter setting does not conflict with the setting for Cd01
(Set frequency source).
Ex: If Cd01=1 then the parameter CE61 cann’t be modify to 2 ,4 or 7.