4
YOUR ULTIMATE ALLY IN POWER
LX1500GAVR
USER MANUAL
FEATURES
1
1 . Power Switch
8
USB
2
2 . Power On Indicator
3 . LCD module display
4 . Display/Select button
7
WIRING FAULT
3
9
5 . Battery backup and Surge Protected Outlets
10 10
6 . Full-Time Surge Protected Outlets
INSTALLING YOUR UPS SYSTEM - Continued
BASIC OPERATION
HARDWARE INSTALLATION GUIDE
4 . Press the power switch to turn the
1 . Power Switch: Used as the master on/
7 . Circuit Breaker: Located on the back
1 . Your new UPS may be used
unit on. The Power On indicator light
off switch for equipment connected to
of the UPS, the circuit breaker serves to
immediately upon receipt. However,
will illuminate and the unit will “beep”.
the battery power supplied outlets.
provide overload and fault protection.
after receiving a new UPS, to ensure
If an overload is detected, an audible
2 . Power On Indicator: This LED is
8 . USB Ports to PC: The USB port allows
the battery’s maximum charge capacity,
alarm will sound and the unit will emit
illuminated when the utility power
connection and communication
it is recommended that you charge the
one long beep. To correct this, turn the
is normal and the UPS outlets are
between the computer and the UPS
battery for at least 8 hours. Your UPS is
UPS off and unplug at least one piece
providing power, free of surges and
unit.
equipped with an auto-charge feature.
of equipment from the battery power
spikes.
9 . Wiring Fault Indicator (red): This
When the UPS is plugged into an AC
supplied outlets. Make sure the circuit
3 . LCD module display: High resolution
LED indicator will illuminate to warn
outlet, the battery will automatically
breaker is depressed and then turn the
and intelligent LCD display shows all
the user that a wiring problem exists,
charge whether the UPS is turned on or
UPS on.
the UPS information using icons and
such as bad ground, missing ground or
off.
5 . To maintain optimal battery charge,
messages. For more information please
reversed wiring. If this is illuminated,
Note: This UPS is designed with a
leave the UPS plugged into an AC
review the “Definitions for Illuminated
disconnect all electrical equipment
safety feature to keep the system from
outlet at all times.
LCD Indicators” section below.
from the outlet and have an electrician
being turned on during shipment. The
6 . To store the UPS for an extended
4 . Display/Select button: The button
verify the outlet is properly wired. The
first time you turn the UPS on, you will
period, cover it and store with the
can be used to select the LCD display
unit will not provide surge protection
need to have it connected to AC power
battery fully charged. While in storage,
contents including Input Voltage,
without being plugged into a grounded
or it will not power up.
recharge the battery every three
Output Voltage, and Estimated Run
and properly wired wall outlet.
2 . With the UPS unit turned off and
months to ensure battery life.
Time. Short press the button to scroll
10
. Widely Spaced Outlets Designed for
unplugged, connect your computer,
7 . Ensure the wall outlet and UPS are
down the function menu. Pressing the
AC Adapters: The unit has 2 widely
monitor, and any other peripherals
located near the equipment being
button for 3 seconds will keep the
spaced outlets to allow AC power
requiring battery backup into the
attached for proper accessibility.
LCD display always on or turn the LCD
adapter blocks to be plugged into the
battery power supplied outlets. DO
display off while in AC/Utility power
UPS without blocking adjacent outlets.
Battery Backup & Surge Protection
Press to Reset
7 . Circuit Breaker
8 . USB Ports to PC
9 . Wiring Fault Indicator (red)
mode. For more information about the
10 . Widely Spaced Outlets Designed for AC Adapters
NOT plug a laser
printer, paper Down/Display Button, please refer to
shredder, copier, the Function Setup Guide.
space heater, 5 . Battery backup and Surge Protected
vacuum, sump Outlets: The unit has 5 battery
pump or other large electrical devices powered/surge suppression outlets
into the “Battery and Surge Protected
PLUG IN
for connected equipment to ensure
Outlets”. The power demands of these temporary uninterrupted operation
devices may overload and damage the of your equipment during a power
unit. failure. (DO NOT plug a laser printer,
Surge Protection
65
1500
PRODUCT REGISTRATION
Thank you for purchasing a CyberPower product. Please take a few minutes to register your product at www.cyberpowersystems.com/registration/. Registration certifies your product's
warranty, confirms your ownership in the event of a product loss or theft and entitles you to free technical support. Register your product now to receive the benefits of CyberPower ownership.
IMPORTANT SAFETY WARNINGS (SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions
carefully during installation and operation of the unit. Read this manual thoroughly before
attempting to unpack, install, or operate your UPS.
CAUTION! To prevent the risk of fire or
electric shock, install in a temperature
and humidity controlled indoor area free
of conductive contaminants. (Please see
specifications for acceptable temperature
and humidity range).
CAUTION! To reduce the risk of electric
shock, do not remove the cover except to
service the battery. Turn off and unplug the
unit before servicing the batteries. There
are no user serviceable parts inside except
for the battery.
CAUTION! Hazardous live parts inside can
be energized by the battery even when the
AC input power is disconnected.
CAUTION! The UPS must be connected
to an AC power outlet with fuse or circuit
breaker protection. Do not plug into an
outlet that is not grounded. If you need to
de-energize this equipment, turn off and
unplug the unit.
CAUTION! To avoid electric shock, turn off
the unit and unplug it from the AC power
source before servicing the battery or
installing a computer component.
CAUTION! Not for use in a computer
room as defined in the Standard for the
Protection of Electronic Computer/Data
Processing Equipment, ANSI/NFPA 75.
CAUTION! To reduce the risk of fire,
connect only to a circuit provided with
20 amperes maximum branch circuit over
current protection in accordance with the
National Electric Code, ANSI/NFPA 70.
CAUTION! DO NOT USE FOR MEDICAL
OR LIFE SUPPORT EQUIPMENT! DO NOT
use in any circumstance that would affect
the operation and safety of life support
equipment, medical applications, or patient
care.
CAUTION! DO NOT USE WITH OR NEAR
AQUARIUMS! To reduce the risk of fire
or electric shock, do not use with or near
an aquarium. Condensation from the
aquarium can cause the unit to short out.
CAUTION! DO NOT USE THE UPS ON ANY
TRANSPORTATION! To reduce the risk of
fire or electric shock, do not use the unit
on any transportation such as airplanes
or ships. The effect of shock or vibration
caused during transit and the damp
environment can cause the unit to short out.
Cyber Power Systems (USA), Inc.
3 . Plug the UPS into a 2 pole, 3 wire
grounded receptacle (wall outlet).
Make sure the wall branch outlet is
protected by a fuse or circuit breaker
and does not service equipment with
large electrical demands (e.g. air
conditioner, copier, etc.…). The warranty
prohibits the use of extension cords,
outlet strips, and surge strips.
REPLACING THE BATTERY
Replacement of batteries located in an OPERATOR ACCESS AREA.
1 . When replacing batteries, replace with the same number of the following battery:
CyberPower / RB1270X2C for the LX1500GVAR.
2 . CAUTION! Risk of Energy Hazard, 24 V, maximum 9 Ampere-hour battery. Before
replacing batteries, remove conductive jewelry such as chains, wrist watches, and
rings. High energy conducted through these materials could cause severe burns.
3 . CAUTION! Do not dispose of batteries in a fire. The batteries may explode.
4 . CAUTION! Do not open or mutilate batteries. Released material is harmful to the skin
and eyes. It may be toxic.
5 . CAUTION: A battery can present a risk of electrical shock and high short circuit
current. The following precautions should be observed when working on batteries:
1) Remove watches rings, or other metal objects.
2) Use tools with insulated handles.
CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE.
DISPOSE OF USED BATTERIES ACCORDING TO LOCAL REGULATIONS.
1 2 3
6 7
(+)Red
(-)Black
paper shredder, copier, space heater,
vacuum, sump pump or other large
electrical devices into the “Battery
and Surge Protected Outlets”. The
power demands of these devices may
overload and damage the unit.)
6 . Full-Time Surge Protected Outlets: The
unit has 5 surge suppression outlets
without battery backup.
BATTERY REPLACEMENT PROCEDURE:
1 . Switch off and unplug all the connected equipment.
2 . Switch off the UPS and disconnect it from the wall outlet.
3 . Place the product on its side, on a solid and stable surface.
4 . Loosen the battery compartment cover screws.
5 . Press on the locking latch and slide the battery compartment cover.
6 . Disconnect the battery wires from the right side of the battery and then take it out of
the battery compartment.
7 . Disconnect the battery wires from the remaining battery.
8 . Slide the remaining battery from left to right and remove it from the compartment.
9 . Install the "left side" replacement battery by connecting the yellow wire (+) to the red
connector from the battery and the black wire (-) to the black connector from the
battery. Place the battery into the left side of the compartment.
10 . Install the "right side" replacement battery by connecting the red wire (+) to the
red connector from the battery and yellow wire (-) to the black connector from the
battery. Place the battery into the right side of the compartment. Note: Only new
batteries should be used for replacement and both batteries should be replaced at
the same time to ensure maximum life span.
1 1 . Close the battery compartment cover and secure it with the screws.
1 2 . Recharge the UPS for 8-16 hours to fully charge the battery.
4 5
8
(-)Black
(+)Red
INSTALLING YOUR UPS SYSTEM
UNPACKING
Inspect the UPS upon receipt. The box
should contain the following:
(a) UPS unit
(b) User’s manual
(c) USB A+B type cable
(d) Function Setup Guide
*PowerPanel® Personal software is
available on our website. Please visit
www.CyberPowerSystems.com and go to
the Software Section for free download.
OVERVIEW
The LX1500GAVR provides complete
power protection from utility power
that is not always consistent. The
LX1500GAVR features 890 Joules of surge
protection. The unit provides long lasting
battery backup during power outages
with maintenance free batteries. The
LX1500GAVR ensures consistent power
to your computer system and includes
software that will automatically save your
open files and shutdown your computer
system during a utility power loss.
AUTOMATIC VOLTAGE REGULATOR
The LX1500GAVR uses Automatic Voltage
Regulation (AVR) to stabilize inconsistent
utility power voltage to levels that are
safe for connected equipment. AVR
safeguards hardware and important data
files by automatically increasing low utility
power to a consistent and safe output
voltage while preserving battery power for
outages.
DETERMINE THE POWER REQUIREMENTS
OF YOUR EQUIPMENT
1 . Ensure that the equipment plugged
into the outlet does not exceed the
UPS’s rated capacity 1500VA/900W
for LX1500GAVR. If the rated capacity
of the unit is exceeded, an overload
condition may occur and cause the
UPS to shut down or the circuit breaker
to trip.
2 . There are many factors that can
affect the amount of power that your
computer system will require. It is
suggested that the load placed on the
battery outlets not exceed 80% of the
unit’s capacity.
REMINDER: Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Most retailers that sell lead-acid batteries collect used batteries for recycling, as required by
local regulations.