Intelligent PDU User Guide
To set near overload threshold at 10A
CyberPower > devcfg nearover 10
Example 4:
To set cold start delay at 0
CyberPower > devcfg coldstadly -1
Example 5:
To set idle time of the device at 10 minutes
CyberPower > devcfg idletime 10
bankcfg
Description: Show and set bank load configuration.
Show information of bank load threshold.
<overload threshold value>
Set bank overload threshold value.
<near overload threshold value>
Set bank near overload threshold value.
<low load threshold value>
Set bank low load threshold value.
Set outlet restriction of bank
Example 1:
To display bank load configuration
CyberPower > bankcfg show
Example 2:
To set overload threshold of bank 1 at 15A
CyberPower > bankcfg index b1 overload 15
Example 3:
To set near overload threshold of bank 2 at 10A
CyberPower > bankcfg index b2 nearover 10
oltsta
Description: Show information of outlet status.
Show information of outlet status.