2.
TEMPERATURE
ADJUSTMENT
&
CONTROL
1) TEMPERATURE ADJUSTMENT
1.1- TEMPERATURE ADJUSTMENT
TEMP CONTROL DIAL is rotated VAC , LOW, MIDDLE, HIGH, SUPER.
TEMPERATURE will be set if the Dial doesnt get rotated again within 5 sec
1.2- FORCED DEFROST : Button of M-PCB(SW2) is pushed 1 time.
1.3- SHORT CIRCUIT OPERATION : Button of M-PCB(SW2) is pushed 2 times.
2 )TEMPERATURE CONTROL
2.1- COMP will be controlled by the on/off point of R-Sensor at each mode.
2.2- STEP DIFF of ROOM R : 1.4 deg
2.3- Middle OFF point of ROOM R : -0.15°C
2.4- ON/OFF DIFF of ROOM R : 3 deg
ON -í
OFF
2.85¡É
-0.15¡É
5.65¡É
2.65 ¡É
0.05 ¡É
-2.95¡É
1.25¡É
-1.55¡É
1.45¡É
4.25¡É
3 )FORCED DEFROST
3.1- Defrost mode will be Started independent of the cycle.
3.2- The flow is same as the general defrost mode flow.
4 )SHORT CIRCUIT OPERATION
4.1- COMP & FAN will be on independent of the operation condition.
4.2-The time limit of SHORT CIRCUIT OPERATION: 60 hrs
3.
VACATION
- Rotate TEMP. CONTROL Dial and make Vacation Location.
ON POINT: 5.65°C
OFF POINT: 2.65°C