6 | Unit installation
Installer reference guide
25
2MXM40+50A
R32 Split series
4P600463-4E – 2021.12
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-
ventilated room without continuously operating ignition sources (e.g. open flames,
an operating gas appliance, or an operating electric heater). The room size shall be as
specified in the General safety precaution.
6.1.1 Installation site requirements of the outdoor unit
INFORMATION
Also read the following requirements:
"2General safety precautions"[47].
"7.1.3Refrigerant piping length and height difference"[433].
Mind the following spacing guidelines:
Wall facing 1 side:
(mm)
>50
a
b
>100
<1200
a
b
Wall facing 2 sides:
(mm)
>100
>50
b
a
>150
>50
b
a
Wall facing 3 sides:
(mm)
>150
>50
>300
b
a
a Air outlet
b Air inlet
Allow 300mm of work space below the ceiling surface and 250mm for piping and
electrical servicing.
>250
>300
(mm)
NOTICE
Do NOT stack the units on each other.
Do NOT hang the unit on a ceiling.

Table of Contents

Other manuals for Daikin 2MXM40A2V1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXM40A2V1B and is the answer not in the manual?

Daikin 2MXM40A2V1B Specifications

General IconGeneral
BrandDaikin
Model2MXM40A2V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals