Troubleshooting for Outdoor Unit SiUS121502E
150 Service Diagnosis
7.11 Four Way Valve Abnormality
Error Code
EA
Outdoor Unit LED
Display
A
j
1
i
2
h
3
h
4
h
5
h
Method of Error
Detection
The liquid pipe thermistor and the outdoor heat exchanger thermistor are checked to see if they
function within their normal ranges in the operating mode.
Error Decision
Conditions
A following condition continues for A seconds after the compressor has started.
Cooling operation
The lowest liquid pipe temperature among the rooms in operation –Tde > 45°C (81°F)
Heating operation
The highest liquid pipe temperature among the rooms in operation –Tde < 0°C (0°F)
Tde: outdoor heat exchanger temperature
Supposed
Causes
Disconnection of four way valve coil
Defective four way valve, coil, or harness
Defective outdoor unit PCB
Defective thermistor
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Cooling Heating
A (seconds) 240 1

Table of Contents

Other manuals for Daikin 2MXS-N Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXS-N Series and is the answer not in the manual?

Daikin 2MXS-N Series Specifications

General IconGeneral
BrandDaikin
Model2MXS-N Series
CategoryHeat Pump
LanguageEnglish

Related product manuals