Troubleshooting for Outdoor Unit SiUS121736EA
201 Service Diagnosis
7.16 CT or Related Abnormality
Error Code H8
Outdoor Unit LED
Display
A j 1 i 2 i 3 h 4 h 5 h
Method of Error
Detection
A CT or related error is detected by checking the compressor running frequency and CT-detected
input current.
Error Decision
Conditions
The compressor running frequency is more than A Hz and input current is less than B A.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective power module
Broken or disconnected wiring
Defective reactor
Defective outdoor unit PCB
A (Hz) B (A)
18/24 class 32 0.5
36 class 55 0.5

Table of Contents

Other manuals for Daikin 2MXS18NMVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXS18NMVJU and is the answer not in the manual?

Daikin 2MXS18NMVJU Specifications

General IconGeneral
Cooling Capacity5.0 kW
RefrigerantR-32
Power Supply220-240V, 50Hz
Number of Connectable Indoor Units2
TypeMulti Split
Energy Efficiency Ratio (Heating)11.2 BTU/W
Seasonal Energy Efficiency Ratio (SEER)6.10
Indoor Unit Noise Level19 dB(A)
Indoor Unit Dimensions (WxHxD)Varies depending on the connected indoor unit model
Indoor Unit WeightVaries depending on the connected indoor unit model

Related product manuals