Control Specification SiUS121827E
108 Part 4 Functions and Control
4.4.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(The function is not used when defrosting.)
Cooling Heating
A (Hz) 35 23
B (Hz) 48 48
C (Hz) 65 65
D (Hz) 83 83
E (Hz) 95 95
F (seconds) 120
G (seconds) 270 ~ 420
H (seconds) 290 ~ 450
J (seconds) 170 ~ 250
K (seconds) 150 ~ 220
(sec.)
Time
(R23251)
(Hz)
Frequency
C
D
E
B
FGHJK
A