Field Settings SiUS121827E
272 Part 7 Trial Operation and Field Settings
Wireless Remote
Controller
Address
Factory set is 1. Change the wireless remote controller address setting by the following steps, if
necessary.
1. Hold down button and /TEST button at the same time for at least 4 seconds to enter the
field setting mode. (SETTING is indicated on the display).
Press FAN button and select display setting ( or ). Each time the button is pressed, the
display switches between and .
2. Press button and button to set the address.
Address can be set from 1 ~ 6, but set it to 1 ~ 3 and to same address as the transmitter board.
The transmitter board does not work with address 4 ~ 6.
3. Press RESERVE button to confirm the setting.
4. Hold down /TEST button to quit the field setting mode and return to the normal display.
Field setting mode
Address
Multiple setting
(R14401)