EasyManua.ls Logo

Daikin AGZ030E - Warranty Registration Form (Scroll) (Continued)

Daikin AGZ030E
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WarranTy regIsTraTIon form (sCroll)
www.DaikinApplied.com 105 IOM 1206-7 • TRAILBLAZER
MODEL AGZ CHILLERS
6/12/15 MLP
Control # - SF99007
2
L. Does all field wiring conform to unit electrical specifications?
M. Are all service and liquid line valves in correct position?
N. Water Strainer installed? Shell & Tube Evaporators 0.125”(3.175mm) or smaller perforations
Brazed Plate Evaporator 0.063” (1.6mm) or smaller perforations
O. Has a flow switch been installed per the IM manual?
P. Has the chill water circuit been cleaned, flushed, and water treatment confirmed?
Q. Does the chiller and condenser water piping conform to the IM manual?
R. Are fans properly aligned and turn freely?
S. Is wind impingement against the air cooled condenser a consideration?
T. Description of unit location with respect to building structures. Include measured distances.
Description:
III. REFRIGERATION SYSTEM
N/A YES NO
A. Has all field piping been leak tested at 150 psig (690 kPA)?
B. Has system been properly evacuated and charged?
C. Refrigerant R- Circuit 1 lbs (kg) Circuit 2 lbs. (kg)
D. Does piping to unit appear to be adequately sized and installed according to the IM bulletin?
E. Is a liquid line filter-drier installed in each circuit?
F. Is level of oil in sightglass visible butnot more than 1/2 glass with compressors running?
G. Is a liquid line solenoid installed correctly in each circuit?
H. Is expansion valve bulb or suction sensor properly installed and insulated?
IV. DESIGN CONTROLS
A. CHILLER
Water Pressure Drop:
psig(kPa)
Ft. (kPa)
gpm (lps)
Water Temperatures: Entering °F (°C) Leaving °F (°C)
B. CONDENSER
Water Pressure Drop:
psig(kPa)
Ft. (kPa)
gpm (lps)
Water Temperatures: Entering °F (°C) Leaving °F (°C)
V. START-UP
YES NO
A. Does unit start and perform per sequence of operation as stated in the IM Manual?
B. Do condenser fans rotate in the proper directions?