IOM 1206-7 • TRAILBLAZER
MODEL AGZ CHILLERS 8 www.DaikinApplied.com
InsTallaTIon and applICaTIon InformaTIon
Models AGZ140-240E:
The Case 5 gures for models AGZ140-240E show adjustment
factors for pit/wall heights of 6 feet, 8 feet, and 10 feet.
Figure 17: Case 5 - Full Load Capacity Reduction
(AGZ140-180E)
Figure 18: Case 5 - Full Load Capacity Reduction
(AGZ190-240E)
Figure 19: Case 5 - Power Increase (AGZ140-210E)
Figure 20: Case 5 - Power Increase (AGZ225-240E)
0.0
1.0
2.0
3.0
4.0
5.0
6.0
0 8 10 12 13 14
% Capacity Reduction
Depth of Pit / Wall Height (ft)
Full Load Capacity Reduction (AGZ140-180E)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
0 8 10 12 13 14
% Capacity Reduction
Depth of Pit / Wall Height (ft)
Full Load Capacity Reduction (AGZ190-240E)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
0 8 10 12 13 14
% Power Increase
Depth of Pit / Wall Height (ft)
Power Increase (AGZ140-210E)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
0 8 10 12 13 14
% Power Increase
Depth of Pit / Wall Height (ft)
Power Increase (AGZ225-240E)
Distance = 6 ft Distance = 8 ft Distance = 10 ft