3 | Components
Service manual
94
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
CAUTION
Make sure to open the valve (if equipped) towards the expansion vessel, otherwise
the overpressure will be generated.
13 Open the stop valves and add water to the water circuit if needed, see
"4.3.2Repair procedures"[4302].
Is the problem solved? Action
Yes No further actions required.
No Return to the troubleshooting of the
specific error and continue with the
next procedure.
To install the 3-way valve motor
CAUTION
Make sure the 3‑way valve body axle is aligned with the 3‑way valve motor when
installing the 3‑way valve motor on the 3‑way valve body.The 3‑way valve motor is
shipped with the 3‑way valve knob in the central position.
1 Check the position of the notch in the 3‑way valve body axle.
a
e
c
d