6 Electrical installation
Installation manual
15
EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3
Daikin Altherma 3 M
4P685229-1A – 2022.05
Outdoor water piping insulation
NOTICE
Outside piping. Make sure the outside piping is insulated
as instructed to protect against hazards.
For piping in free air, it is recommended to use the insulation
thickness as shown in below table as a minimum (with λ=0.039W/
mK).
Piping length (m) Minimum insulation thickness
(mm)
<20 19
20~30 32
30~40 40
40~50 50
For other cases the minimum insulation thickness can be determined
using the Hydronic Piping Calculation tool.
The Hydronic Piping Calculation tool is part of the Heating Solutions
Navigator which can be reached via https://
professional.standbyme.daikin.eu.
Please contact your dealer if you have no access to Heating
Solutions Navigator.
This recommendation ensures good operation of the unit, however,
local regulations may differ and shall be followed.
6 Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
Do NOT push or place redundant cable length in the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50mm.
6.1 About electrical compliance
Equipment complying with EN/IEC 61000‑3‑12 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16A and ≤75A per phase.).
6.2 Guidelines when connecting the
electrical wiring
Tightening torques
Item Tightening torque (N•m)
X1M 2.45 ±10%
X2M 0.88 ±10%
X3M 0.88 ±10%
X4M 2.45 ±10%
X5M 0.88 ±10%
X7M 0.88 ±10%
X9M 2.45 ±10%
X10M 0.88 ±10%
6.3 Connections to the outdoor unit
Item Description
Power supply (main) See "6.3.2To connect the main power
supply"[417].
Power supply (backup
heater)
(in case of outdoor unit
with integrated backup
heater)
See "6.3.3To connect the backup heater
power supply"[419].
Backup heater kit +
Bypass valve kit
(in case of external
backup heater kit)
See "6.3.4External backup heater
kit"[420].
User interface See "6.3.5To connect the user
interface"[422].
Shut-off valve See "6.3.6To connect the shut-off
valve"[424].
Electricity meters See "6.3.7To connect the electricity
meters"[425].
Domestic hot water
pump
See "6.3.8To connect the domestic hot
water pump"[425].
Alarm output See "6.3.9To connect the alarm
output"[425].
Space cooling/heating
operation control
See "6.3.10To connect the space cooling/
heating ON/OFF output"[426].
Changeover to
external heat source
control
See "6.3.11To connect the changeover to
external heat source"[426].
Power consumption
digital inputs
See "6.3.12To connect the power
consumption digital inputs"[427].
Safety thermostat See "6.3.13To connect the safety
thermostat (normally closed
contact)"[427].
Smart Grid See "6.3.14To connect a Smart
Grid"[427].