6 Electrical installation
Installation manual
18
EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3
Daikin Altherma 3 M
4P685229-1A – 2022.05
In case of normal kWh rate power supply
Normal kWh rate
power supply
Wires: 1N+GND
Maximum running current: Refer to name
plate on unit.
—
1 Access the electrical connections. See "6.3.1 To connect the
electrical wiring to the outdoor unit"[417].
2 Connect as follows:
NNL NNN PEN
Q1DI
N
L.M1X
NNNNN
N.M1X
N
.M1X
NNNNNNNN
1N~
N
1N~, 50 Hz,
220-240 V AC
NN
3 Fix the cables with cable ties to the cable tie mountings.
In case of preferential kWh rate power supply
Preferential kWh
rate power supply
Wires: 1N+GND
Maximum running current: Refer to name
plate on unit.
Separate normal
kWh rate power
supply
Wires: 1N
Maximum running current: 6.3A
Preferential kWh
rate power supply
contact
Wires: 2×(0.75~1.25mm²)
Maximum length: 50m.
Preferential kWh rate power supply
contact: 16VDC detection (voltage
supplied by PCB). The voltage-free
contact shall ensure the minimum
applicable load of 15VDC, 10mA.
[9.8] Benefit kWh power supply
1 Access the electrical connections. See "6.3.1 To connect the
electrical wiring to the outdoor unit"[417].
2 Connect the preferential kWh rate power supply.
NNL NNN PEN
Q1DI
N
L.M1X
NNNNN
N.M1X
N
.M1X
NNNNNNNN
1N~
N
1N~, 50 Hz,
220-240 V AC
NN
3 If necessary, connect the separate normal kWh rate power
supply.
INFORMATION
Some types of preferential kWh rate power supply require
a separate normal kWh rate power supply to the outdoor
unit. This is required in the following cases:
▪ if the preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the hydro module of the
outdoor unit is allowed at the preferential kWh rate
power supply when active.
5.M2X
6.M2X
L N
1N~, 50 Hz,
230 V AC, 6.3 A