7 Configuration
Installation manual
28
EHVH04+08SU18+23EA
Daikin Altherma 3 R F
4P629088-1C – 2021.11
Domestic hot water
The following setting determines if the system can prepare domestic
hot water or not, and which tank is used. This setting is read only.
# Code Description
[9.2.1] [E‑05]
(a)
[E‑06]
(a)
[E‑07]
(a)
▪ Integrated
The backup heater will also be used
for domestic hot water heating.
(a)
Use the menu structure instead of the overview settings. Menu
structure setting [9.2.1] replaces the following 3 overview settings:
• [E-05]: Can the system prepare domestic hot water?
• [E-06]: Is a domestic hot water tank installed in the system?
• [E-07]: What kind of domestic hot water tank is installed?
Emergency
When the heat pump fails to operate, the backup heater can serve
as an emergency heater. It then takes over the heat load either
automatically or by manual interaction.
▪ When Emergency is set to Automatic and a heat pump failure
occurs, the backup heater automatically takes over the domestic
hot water production and space heating.
▪ When Emergency is set to Manual and a heat pump failure
occurs, the domestic hot water heating and space heating stops.
To manually recover it via the user interface, go to the
Malfunctioning main menu screen and confirm whether the
backup heater can take over the heat load or not.
▪ Alternatively, when Emergency is set to:
▪ auto SH reduced/DHW on, space heating is reduced but
domestic hot water is still available.
▪ auto SH reduced/DHW off, space heating is reduced and
domestic hot water is NOT available.
▪ auto SH normal/DHW off, space heating operates as
normally but domestic hot water is NOT available.
Similarly as in Manual mode, the unit can take the full load with
the backup heater if the user activates this via the
Malfunctioning main menu screen.
To keep energy consumption low, we recommend to set Emergency
to auto SH reduced/DHW off if the house is unattended for longer
periods.
# Code Description
[9.5.1] [4-06] ▪ 0: Manual
▪ 1: Automatic
▪ 2: auto SH reduced/DHW on
▪ 3: auto SH reduced/DHW off
▪ 4: auto SH normal/DHW off
INFORMATION
The auto emergency setting can be set in the menu
structure of the user interface only.
INFORMATION
If a heat pump failure occurs and Emergency is set to
Manual, the room frost protection function, the underfloor
heating screed dryout function, and the water pipe
antifreeze function will remain active even if the user does
NOT confirm emergency operation.
Number of zones
The system can supply leaving water to up to 2 water temperature
zones. During configuration, the number of water zones must be set.
INFORMATION
Mixing station. If your system layout contains 2 LWT
zones, you need to install a mixing station in front of the
main LWT zone.
# Code Description
[4.4] [7‑02] ▪ 0: Single zone
Only one leaving water temperature
zone:
a Main LWT zone
[4.4] [7‑02] ▪ 1: Dual zone
Two leaving water temperature zones.
The main leaving water temperature
zone consists of the higher load heat
emitters and a mixing station to
achieve the desired leaving water
temperature. In heating:
a Additional LWT zone: Highest
temperature
b Main LWT zone: Lowest temperature
c Mixing station
NOTICE
NOT configuring the system in the following way can cause
damage to the heat emitters. If there are 2 zones, it is
important that in heating:
▪ the zone with the lowest water temperature is
configured as the main zone, and
▪ the zone with the highest water temperature is
configured as the additional zone.
NOTICE
If there are 2 zones and the emitter types are wrongly
configured, water of high temperature can be sent towards
a low temperature emitter (underfloor heating). To avoid
this:
▪ Install an aquastat/thermostatic valve to avoid too high
temperatures towards a low temperature emitter.
▪ Make sure you set the emitter types for the main zone
[2.7] and for the additional zone [3.7] correctly in
accordance with the connected emitter.