5 Application guidelines
Installer reference guide
15
EPGA11~16DAV3 + EABH/X16DA6V+9W
Daikin Altherma – Low temperature split
4P556069-1 – 2018.10
For the additional zone:
The heatpump convectors are directly connected to the indoor
unit.
The desired room temperature is set via the remote controller of
the heatpump convectors for each room.
The heating or cooling demand signals of each heat pump
convector are connected in parallel to the digital input on the
indoor unit (X2M/35 and X2M/30). The indoor unit will only
supply the desired additional leaving water temperature when
there is an actual demand.
The user interface connected to the indoor unit decides the space
operation mode. Mind that the operation mode on each remote
controller of the heat pump convectors must be set to match the
indoor unit.
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
2 (Room thermostat): Unit
operation is decided based on
the ambient temperature of the
user interface.
Note:
Main room = user interface
used as room thermostat
functionality
Other rooms = external room
thermostat functionality
Number of water temperature
zones:
#: [4.4]
Code: [7-02]
1 (Dual zone): Main + additional
In case of heatpump convectors:
External room thermostat for the
additional zone:
#: [3.A]
Code: [C-06]
1 (1 contact): When the used
external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition. No separation between
heating or cooling demand.
Shut-off valve output Set to follow the thermo demand
of the main zone.
Shut-off valve If the main zone must be shut off
during cooling mode to prevent
condensation on the floor, set it
accordingly.
At the mixing valve station Set the desired main leaving
water temperature for heating
and/or cooling.
Benefits
Comfort.
The smart room thermostat functionality can decrease or
increase the desired leaving water temperature based on the
actual room temperature (modulation).
The combination of the two heat emitter systems provides the
excellent heating comfort of the under floor heating, and the
excellent cooling comfort of the heatpump convectors.
Efficiency.
Depending on the demand, the indoor unit supplies different
leaving water temperature matching the design temperature of
the different heat emitters.
Underfloor heating has the best performance with Altherma LT.
5.3 Setting up an auxiliary heat source
for space heating
Space heating can be done by:
The indoor unit
An auxiliary boiler (field supply) connected to the system
When the room thermostat requests heating, the indoor unit or the
auxiliary boiler starts operating depending on the outdoor
temperature (status of the changeover to external heat source).
When the permission is given to the auxiliary boiler, the space
heating by the indoor unit is turned OFF.
Bivalent operation is only possible for space heating, NOT for
domestic hot water production. Domestic hot water is always
produced by the DHW tank connected to the indoor unit.
INFORMATION
During heating operation of the heat pump, the
heat pump operates to achieve the desired
temperature set via the user interface. When weather-
dependent operation is active, the water temperature is
determined automatically depending on the outdoor
temperature.
During heating operation of the auxiliary boiler, the
auxiliary boiler operates to achieve the desired water
temperature set via the auxiliary boiler controller.
Setup
Integrate the auxiliary boiler as follows:
NOTICE
Make sure the auxiliary boiler and its integration in the
system complies with applicable legislation.
Daikin is NOT responsible for incorrect or unsafe
situations in the auxiliary boiler system.
Make sure the return water to the heatpump does NOT exceed
55°C. To do so:
Set the desired water temperature via the auxiliary boiler
controller to maximum 55°C.
Install an aquastat valve in the return water flow of the
heatpump. Set the aquastat valve to close above 55°C and to
open below 55°C.
Install non-return valves.
Make sure to only have one expansion vessel in the water circuit.
An expansion vessel is already pre-mounted in the indoor unit.
Install the digital I/O PCB (option EKRP1HB).
Connect X1 and X2 (changeover to external heat source) on the
digital I/O PCB to the auxiliary boiler thermostat.
To setup the heat emitters, see "5.2Setting up the space heating/
cooling system"on page10.
Configuration
Via the user interface (quick wizard):
Set the use of a bivalent system as external heat source.
Set the bivalent temperature and hysteresis.
Changeover to external heat source decided by an auxiliary
contact
Only possible in external room thermostat control AND one
leaving water temperature zone (see "5.2 Setting up the space
heating/cooling system"on page10).