8 Configuration
Installer reference guide
52
EPGA11~16DAV3 + EABH/X16DA6V+9W
Daikin Altherma – Low temperature split
4P556069-1 – 2018.10
# Code Description
[3.8.2] [9-06] Heating maximum
[2‑0D]=2 (emitter type additional zone
= radiator)
37°C~60°C
Else: 37°C~55°C
[3.8.3] [9-07] Cooling minimum: 5°C~18°C
[3.8.4] [9-08] Cooling maximum: 8°C~22°C
Control
The control type is displayed here, but cannot be adjusted. It is
determined by the control type of the main zone. For more info about
the functionality, see "8.4.3Main zone"on page47.
# Code Description
[3.9] N/A Control
Leaving water if the control type of the
main zone is Leaving water.
External room thermostat if the control
type of the main zone is External room
thermostat or Room thermostat.
Thermostat type
Only applicable in external room thermostat control. For more info
about the functionality, see "8.4.3Main zone"on page47.
# Code Description
[3.A] [C‑06] External room thermostat type for the
additional zone:
1: 1 contact. Connected to only 1
digital input (X2M/35a)
2: 2 contacts. Connected to 2 digital
inputs (X2M/34a and X2M/35a)
Leaving water temperature: Delta T
For more information, see "8.4.3Main zone"on page47.
# Code Description
[3.B.1] [1-0C] Delta T heating: A minimum temperature
difference is required for the good
operation of heat emitters in heating
mode.
If [2-0D] = 2, this is fixed to 8°C
Else: 3°C~10°C
[3.B.2] [1-0E] Delta T cooling: A minimum temperature
difference is required for the good
operation of heat emitters in cooling
mode.
3°C~10°C
8.4.5 Space heating/cooling
About space operation modes
Depending on your heat pump model, you have to tell the system
which space operation mode to use: heating or cooling.
If a … heatpump
model is installed
Then…
Heating/cooling The system can heat up and cool down a
space. You have to tell the system which
space operation mode to use.
Heating only The system can heat up a space, but
NOT cool down a space. You do NOT
have to tell the system which space
operation mode to use.
To determine if a heating/cooling heat pump model is installed
1 Go to [4]: Space heating/cooling.
2 Check if [4.1] Operation mode is listed and editable.
If so, a heating/cooling heat pump model is installed.
To tell the system which space operation to use, you can:
You can… Location
Check which space operation mode is
currently used.
Home screen
Set the space operation mode permanently. Main menu
Restrict automatic changeover according
to a monthly schedule.
To check which space operation mode is currently used
The space operation mode is displayed on the home screen:
When the unit is in heating mode, the icon is shown.
When the unit is in cooling mode, the icon is shown.
The status indicator shows if the unit is currently in operation:
When the unit is not in operation, the status indicator will show a
blue pulsation with an interval of approximately 5 seconds.
While the unit is in operation, the status indicator will light up blue
constantly.
To set the space operation mode
1 Go to [4.1]: Space heating/cooling > Operation mode
2 Select one of the following options:
Heating: Always heating mode
Cooling: Always cooling mode
Automatic: The operation mode changes
automatically based on the outdoor temperature.
Restricted according to the operation mode
schedule.
Automatic heating/cooling changeover is only applicable for EABX,
EAVX and EAVZ (only with EKHVCONV2 installed).
When Automatic is selected, the changing of the operation mode is
based on the Operation mode schedule [4.2]: the end user indicates
on a monthly base which operation is allowed.
To restrict automatic changeover according to a schedule
Conditions: You set the space operation mode to Automatic.
1 Go to [4.2]: Space heating/cooling > Operation mode
schedule.
2 Select a month.
3 For each month, select an option:
Reversible: Not restricted
Heating only: Restricted
Cooling only: Restricted
4 Confirm the changes.
Example: Changeover restrictions
When Restriction
During cold season.
Example: October, November,
December, January, February and March.
Heating only
During warm season.
Example: June, July and August.
Cooling only
In-between.
Example: April, May and September.
Reversible