EasyManua.ls Logo

Daikin Altherma EBBH11DF6V - To Connect the Changeover to External Heat Source; To Connect the Power Consumption Digital Inputs

Daikin Altherma EBBH11DF6V
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Electrical installation
Installation manual
24
EBBH/X11+16DF
Daikin Altherma 3 R W
4P643600-1B 2021.10
2 Connect the space cooling/heating ON/OFF output cable to the
appropriate terminals as shown in the illustration below.
7
9
YCY2
X2M
12
3
A4P
1+2 Wires connected to the space
cooling/heating ON/OFF
output
3 Wire between X2M and A4P
A4P Installation of EKRP1HBAA is
required.
B
C
A
A
7Y2
B
X2M
C
X2M
A4P
X1M
a
7 9
Y2YC
A4P
a Installation of EKRP1HBAA is required.
3 Fix the cable with cable ties to the cable tie mountings.
6.3.8 To connect the changeover to external
heat source
Wires: 2×0.75mm²
Maximum load: 0.3A, 250VAC
Minimum load: 20mA, 5VDC
[9.C] Bivalent
1 Open the following (see "4.2.1To open the indoor unit"[413]):
1 Front panel
1
2
3
2 Switch box cover
3 Switch box
2 Connect the changeover to external heat source cable to the
appropriate terminals as shown in the illustration below.
B
C
A
A
L N
X1 X2
CB
a
A4P
X2 X3 X4X1
X2X1
X2M
A4P
a Installation of EKRP1HBAA is required.
3 Fix the cable with cable ties to the cable tie mountings.
6.3.9 To connect the power consumption digital
inputs
Wires: 2 (per input signal)×0.75mm²
Power limitation digital inputs: 12VDC / 12mA detection
(voltage supplied by PCB)
[9.9] Power consumption control.
1 Open the following (see "4.2.1To open the indoor unit"[413]):
1 Front panel
1
2
3
2 Switch box cover
3 Switch box
2 Connect the power consumption digital inputs cable to the
appropriate terminals as shown in the illustration below.