8 Configuration
Installer reference guide
70
ERHQ+ERLQ011~016 + EHVH/X11+16S18+26CB
Daikin Altherma – Low temperature split
4P384975-1C – 2018.02
NOTICE
The power saving connector at the outdoor unit shall only
be removed when the main power supply to the application
is switched OFF.
In case of ERLQ004~008CAV3
# Code Description
N/A [E‑08] Power saving function for outdoor unit:
▪ 0: Disabled
▪ 1 (default): Enabled
In case of ERHQ011~016BAV3, ERHQ011~016BAW1,
ERLQ011~016CAV3, and ERLQ011~016CAW1
Do NOT change the default setting.
# Code Description
N/A [E-08] Power saving function for outdoor unit:
▪ 0 (default): Disabled
▪ 1: Enabled
Power consumption control
Only applicable for EHBH/X04+08 + EHVH/X04+08. See
"5Application guidelines"on page11 for detailed information about
this functionality.
Pwr consumpt. control
# Code Description
[A.6.3.1] [4-08] Mode:
▪ 0 (No limitation)(default): Disabled.
▪ 1 (Continuous): Enabled: You can
set one power limitation value (in A
or kW) to which the system power
consumption will be limited for all the
time.
▪ 2 (Digital inputs): Enabled: You can
set up to four different power
limitation values (in A or kW) to
which the system power
consumption will be limited when the
corresponding digital input asks.
# Code Description
[A.6.3.2] [4-09] Type:
▪ 0 (Current): The limitation values are
set in A.
▪ 1 (Power)(default): The limitation
values are set in kW.
[A.6.3.3] [5-05] Value: Only applicable in case of full
time power limitation mode.
0A~50A, step: 1A (default: 50A)
[A.6.3.4] [5-09] Value: Only applicable in case of full
time power limitation mode.
0kW~20kW, step: 0.5kW (default:
20kW)
Amp. limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on current values.
[A.6.3.5.1] [5-05] Limit DI1
0A~50A, step: 1A (default: 50A)
[A.6.3.5.2] [5-06] Limit DI2
0A~50A, step: 1A (default: 50A)
[A.6.3.5.3] [5-07] Limit DI3
0A~50A, step: 1A (default: 50A)
[A.6.3.5.4] [5-08] Limit DI4
0A~50A, step: 1A (default: 50A)
kW limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on power values.
[A.6.3.6.1] [5-09] Limit DI1
0kW~20kW, step: 0.5kW (default:
20kW)
[A.6.3.6.2] [5-0A] Limit DI2
0kW~20kW, step: 0.5kW (default:
20kW)
[A.6.3.6.3] [5-0B] Limit DI3
0kW~20kW, step: 0.5kW (default:
20kW)
[A.6.3.6.4] [5-0C] Limit DI4
0kW~20kW, step: 0.5kW (default:
20kW)
Priority: Only applicable in case of an optional EKHW.