7 Installation
Installation and operation manual
20
EHYKOMB33A
Daikin Altherma hybrid heat pump – gas boiler module
4P353067-1H – 2018.10
Explanation of the flue systems
Category in accordance with CE
C
83
Joint air supply and flue gas discharge duct (CLV system).
Discharging into different pressure zones.
Only as twin pipe system.
C
93
Air supply and flue gas discharge duct in shaft or ducted:
concentric. Air supply from existing duct. Flue gas discharge
via the roof. Air supply and flue gas discharge are in the same
pressure zone.
Concentric flue system between the gas boiler and the duct.
The horizontal flue MUST be installed under a 3° fall towards the
boiler (50mm per metre) and MUST be supported with a minimum
of 1 bracket at each meter length. Best recommended position of the
bracket is just before the joint.
INFORMATION
Flexible flue gas lines may NOT be used in horizontal
connection sections.
C
13
(1) C
33
(2) C
13
(1) C
33
(2)
60/100 60/100 Twin-80 Twin-80
L1 (m) L1 (m) L1 (m) L1 (m)
10 10 80 21
C
13
(1) C
33
(2) C
93
(4) C
53
(3)
80/125 80/125 80/125 80 60/100 60
L1 (m) L1 (m) L1 (m) L2 (m) L1 (m) L2 (m)
29 29 10 25 6 1
1 10
Special remark regarding C
53
: The maximum lengths for L1 and L2
are related to each other. First determine the length of L1; then
make use of the graph below to determine the maximum length of
L2. For example: if the length of L1 is 2m, L2 can maximally be 8m
long.
7
6
5
10
9
11
8
3
4
2
1
0
L2
L1
0 1 2 3 4 6 75
L2=–1.8×L1+11.8
Multi-boiler installation
INFORMATION
All piping lengths in the tables below are maximum
equivalent piping lengths.
L1
L1
C
83
C
43
C
43
6
L2
5
C
83
6
L1
C
43
C
43
5
5
5
L1
L2
L1
L1
L2
The horizontal flue MUST be installed under a 3° fall towards the
boiler (50mm per metre) and MUST be supported with a minimum
of 1 bracket at each meter length. Best recommended position of the
bracket is just before the joint.
INFORMATION
Flexible flue gas lines may NOT be used in horizontal
connection sections.
INFORMATION
The maximum lengths in the table below apply to each gas
boiler separately.
C
83
(6) C
43
(5)
Twin-80 60/100 80/125 Twin-80
L1+L2 (m) L1 (m) L1 (m) L1+L2 (m)
80 10 29 80
Special remark regarding C
83
: Refer to the table below for the
minimum diameters of the combined gas exhaust system.
Number of units Minimum Ø
2 130
3 150
4 180
5 200
6 220
7 230
8 250
9 270
10 280
11 290
12 300
Special remark regarding C
43
: Refer to the table below for the
minimum diameters of the combined gas exhaust/air intake system.