6 Electrical installation
Installation manual
11
ERRA08~12E
Daikin Altherma 3 R MT
4P708481-1 – 2023.02
(a)
MCA=Minimum circuit ampacity. Stated values are maximum
values (see electrical data of combination with indoor units for
exact values).
6.3 Guidelines when connecting the
electrical wiring
Tightening torques
Outdoor unit:
Item Tightening torque (N•m)
X1M 1.47 ±10%
X2M
M4 (earth)
6.4 To connect the electrical wiring to
the outdoor unit
NOTICE
Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Open the service cover. See "4.3 To open the outdoor
unit"[47].
2 Insert the cables at the back of the unit, and route them through
the factory-mounted cable sleeves into the switch box.
a1+a2 Power supply cable (field supply)
b1+b2 Interconnection cable (field supply)
c1+c2 No use
d Cable sleeves (factory-mounted)
3 Inside the switch box, connect the wires to the appropriate
terminals, and fix the cables with cable ties. See:
"6.4.1In case of V3 models"[411]
"6.4.2In case of W1 models"[412]
6.4.1 In case of V3 models
1 Power supply cable:
Route the cable through the frame.
Connect the wires to the terminal block.
Fix the cable with a cable tie.
Wires: 1N+GND
Maximum running current: Refer to name plate on unit.
Q1DI
1N~,
50 Hz,
230 V AC
F1B
1
3
2
4
II
BRN
BLU
YLW/GRN
b
a
L
N
a Power supply cable (field supply)
b Field wiring
F1B Overcurrent fuse (field supply). Recommended fuse: 2
pole, 32A fuse, C curve.
Q1DI Earth leakage circuit breaker (30mA)(field supply)
2 Interconnection cable (indoor↔outdoor):
Route the cable through the frame.
Connect the wires to the terminal block (make sure the
numbers match with the numbers on the indoor unit) and the
earth screw.
Fix the cable with a cable tie.
Wires: (3+GND)×1.5mm²