ESIE09-08A Special Control
Function 61
3.4 Stopping Operation
Operation of the actuator when the system is down, is cleared up.
3.4.1 When System is in Stop Mode
OUTDOOR
INDOOR
Actuator Operation
Compressor OFF
Outdoor unit fan OFF
Four way valve Keep former condition.
Main electronic expansion valve (EV1) 0 pls
Subcooling electronic expansion valve (EV3) 0 pls
Hot gas bypass valve (SVP)
OFF
Ending conditions Request for space heating OR hot water production
Actuator Operation
Compressor OFF
4-way valve Keep former condition.
Pump OFF
Electronic expansion valve K1E - R-410A 0 pls
Electronic expansion valve K2E - R-134a
0 pls
Ending conditions Request for space heating OR hot water production