EasyManuals Logo
Home>Daikin>Air conditioning>CDKD35CVM

Daikin CDKD35CVM User Manual

Daikin CDKD35CVM
298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #198 background imageLoading...
Page #198 background image
Si12-411A Troubleshooting
Service Diagnosis 187
Troubleshooting
Check No.7
Refer to P.210
Check No.8
Refer to P.211
Check No.14
Refer to P.214
Replace the outdoor unit
PCB.
Replace the electrolytic
capacitor.
Inverter checker
Part No.: 1225477
Correct the power supply or
replace the SPM.
(Replace the outdoor unit
PCB.)
(R2844)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Input current flowing
above its stop level?
NO
YES
Normal?
NO
YES
Any LED off?
YES
NO
Check with the inverter checker ().
Turn off the power, and reconnect
the harnesses. Turn on the power
again and get restarted.
Turn off the power and disconnect
the harnesses U, V and W.
Get restarted and measure the
input current.
Check No. 8
Check the discharge pressure.
Check No. 7
Check the installation condition.
Check No. 14
Check the main circuit electrolytic
capacitor.
An input over-current may result from wrong internal wiring. If the wires have been disconnected and
reconnected for part replacement, for example, and the system is interrupted by an input over-current,
take the following procedure.

Table of Contents

Other manuals for Daikin CDKD35CVM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin CDKD35CVM and is the answer not in the manual?

Daikin CDKD35CVM Specifications

General IconGeneral
BrandDaikin
ModelCDKD35CVM
CategoryAir conditioning
LanguageEnglish

Related product manuals