Actuator Check DAMA-SM-21-003
86 Service Diagnosis
5.2 Power Supply Waveform Check
Check No.11 Measure the power supply waveform between No. 1 and No. 2 on the terminal strip, and check
the waveform disturbance.
Check if the power supply waveform is a sine wave (Fig.1).
Check if there is waveform dis
turbance near the zero-cross (sections circled in Fig.2).
5.3 Electronic Expansion Valve Check
Check No.12 Conduct the followings to check the electronic expansion valve (EV).
1. Check if the EV connector is correctly connected to the PCB.
2
. Turn the power off and on again, and check if the EV generates a latching sound.
3. If the EV does not generate a latching sound in the step 2 above, disconnect the connector
and check the continuity using a multimeter.
4. Check the continuity between the pins 5 - 1, 5 - 2, 5 - 3, 5 - 4 (for 5P connectors). If there is
no continuity between the pins, the EV coil is faulty.
5. If the continuity is confirmed in step 3, the outdoor unit PCB (main PCB) is faulty.
[Fig.1] [Fig.2]
Class 18
EV connector P/N 3P651237-1 3P651239-1
Coil Model Name PQ-M10012-001338 PQ-M10012-001339
5P 5 wires
Harness 5P
5P Connector
CheckS20/S21
5 - 1
5 - 2
5 - 3
5 - 4
1 2 3 4 5
DAMA-SM-21-003 -Inverter Multi Split-CTX Series.book Page 86 Wednesday, September 1, 2021 5:44 PM