INSTALLATION INSTRUCTIONS
HEAT PUMP
DZ17VSA HEAT PUMP
INSTALLATION & SERVICE REFERENCE
Index
Important Safety InStructIonS ............................................. 1
ShIppIng InSpectIon .............................................................. 2
codeS & regulatIonS .......................................................... 2
featureS.............................................................................. 2
acceSSorIeS ........................................................................ 2
Before InStallatIon .............................................................2
precautIonS for SelectIng a locatIon ................................. 3
precautIonS for InStallatIon ............................................... 3
InStallatIon clearanceS ......................................................4
cold clImate heat pump operatIon locatIon ...................... 5
rooftop InStallatIonS .........................................................5
electrIcal noISe ................................................................. 5
Safety conSIderatIonS......................................................... 6
meanIngS of SymBolS .......................................................... 6
refrIgerant lIneS ............................................................... 8
refrIgerant lIne connectIonS ........................................... 10
leak teStIng (nItrogen or nItrogen-traced) .................... 10
Stop ValVe operatIon method ........................................... 11
SyStem Start-up procedure .............................................. 11
Start-up procedure detaIl ................................................ 12
electrIcal connectIonS ....................................................12
Step 1. calculate refrIgerant charge BaSed on
lIne Set length .......................................................... 16
Step 2. connect heat pump to SyStem .............................. 18
Step 3. SyStem Start-up teSt ............................................ 18
addItIonal charge adjuStIng procedure .......................... 18
Step 4. adjuSt refrIgerant leVel ..................................... 18
Step 5. meaSure SuBcoolIng to VerIfy proper charge ..... 18
heat pump wIth outdoor temperature lockoutS ............... 19
wIrIng dIagram ................................................................ 20
teStIng capacItor reSIStance ............................................22
coolIng analySIS chart .................................................... 24
heatIng analySIS chart ..................................................... 25
trouBleShootIng ...............................................................26
SettIng the mode dISplay .................................................. 31
7-Segment dISplay ............................................................. 37
heat pump homeownerS routIne maIntenance
recommendatIonS ........................................................ 40
Start up checklISt ........................................................... 41
ctk04 addendum ............................................................... 43
Important Safety InStructIonS
The following symbols and labels are used throughout this
manual to indicate immediate or potential safety hazards. It is
the owner’s and installer’s responsibility to read and comply
with all safety information and instructions accompanying
these symbols. Failure to heed safety information increases
the risk of personal injury, property damage, and/or product
damage. Also see “Meanings of Symbols” on page 6.
WARNING
HIGH VOLTAGE !
dISconnect all power Before SerVIcIng.
multIple power SourceS may Be preSent. faIlure
to do So may cauSe property damage, perSonal
Injury or death.
WARNING
only perSonnel that haVe Been traIned to InStall, adjuSt, Ser-
VIce or repaIr (hereInafter, “SerVIce”) the equIpment SpecIfIed
In thIS manual Should SerVIce the equIpment. the manufacturer
wIll not Be reSponSIBle for any Injury or property damage arIS-
Ing from Improper SerVIce or SerVIce procedureS. If you SerVIce
thIS unIt, you aSSume reSponSIBIlIty for any Injury or property
damage whIch may reSult. In addItIon, In jurISdIctIonS that re-
quIre one or more lIcenSeS to SerVIce the equIpment SpecIfIed In
thIS manual, only lIcenSed perSonnel Should SerVIce the equIp-
ment. Improper InStallatIon, adjuStment, SerVIcIng or repaIr of
the equIpment SpecIfIed In thIS manual, or attemptIng to InStall,
adjuSt, SerVIce or repaIr the equIpment SpecIfIed In thIS manual
wIthout proper traInIng may reSult In product damage, property
damage, perSonal Injury or death.
prop 65 warnIng
for calIfornIa conSumerS
WARNING
-
www.P65Warnings.ca.gov
CAUTION
do not waSh the heat pump wIth exceSSIVe water. an electrIc
Shock or fIre could reSult.
English
Français
Español
Our continuing commitment to quality products may mean a change in specications without notice.
© 2013, 2017-2019
Daikin Texas Technology Park,19001 Kermier Road,Waller, TX, 77484, U.S.A.
www.daikincomfort.com
3P515859-3P

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Daikin DZ17VSA301AA and is the answer not in the manual?

Daikin DZ17VSA301AA Specifications

General IconGeneral
Model NumberDZ17VSA301AA
CategoryHeat Pump
Cooling Capacity (BTU/h)30000
SEER Rating17
HSPF Rating9.5
Refrigerant TypeR-410A
Compressor TypeInverter
StagesVariable Speed
Voltage208/230
Phase1
Heating Capacity (BTU/h)30000

Summary

IMPORTANT SAFETY INSTRUCTIONS

PRECAUTIONS FOR SELECTING A LOCATION

PRECAUTIONS FOR INSTALLATION

Critical considerations during the installation process.

INSTALLATION CLEARANCES

SAFETY CONSIDERATIONS

REFRIGERANT LINES

REFRIGERANT LINE CONNECTIONS

LEAK TESTING (NITROGEN OR NITROGEN-TRACED)

Procedure for testing the system for refrigerant leaks.

STOP VALVE OPERATION AND SYSTEM START-UP

STOP VALVE OPERATION METHOD

Detailed instructions on how to operate the stop valves.

SYSTEM START-UP PROCEDURE

General steps for starting up the system.

START-UP PROCEDURE DETAILS

ELECTRICAL CONNECTIONS

Guidelines for making electrical connections to the unit.

HIGH VOLTAGE CONNECTIONS

UNIT SPECIFICATIONS AND WIRING

LOW VOLTAGE CONNECTIONS

Instructions for connecting low voltage communication wires.

STEP 1. CALCULATE REFRIGERANT CHARGE

SYSTEM CONNECTION AND START-UP PROCEDURES

STEP 2. CONNECT HEAT PUMP TO SYSTEM

Procedure for connecting the heat pump to the system.

STEP 5. MEASURE SUBCOOLING TO VERIFY PROPER CHARGE

Verifying correct refrigerant charge by measuring subcooling.

WIRING DIAGRAM (1.5-3.0 ton)

TESTING CAPACITOR RESISTANCE

COOLING ANALYSIS CHART

HEATING ANALYSIS CHART

TROUBLESHOOTING

NETWORK TROUBLESHOOTING

HOMEOWNER MAINTENANCE RECOMMENDATIONS

UNITARY INVERTER START-UP CHECKLIST

SYSTEM START-UP TEST PROCEDURE

SET THERMOSTAT TO CHARGE MODE

REFRIGERANT LEVEL ADJUSTMENT AND SUBCOOLING

MEASURE SUBCOOLING TO VERIFY PROPER CHARGE

Method for verifying correct refrigerant charge by measuring subcooling.

COMMUNICATING SYSTEM OVERVIEW

DIAGNOSTICS MENU ACCESS

How to access the system's diagnostic fault history.

SYSTEM SETUP MENUS

SYSTEM SETUP (SYS SET UP1 and SYS SET UP2)

Menus for system configuration and mode settings.

COOL SET-UP

Adjusting cooling performance variables.

ADVANCED FEATURE MENU DETAILS

DIAGNOSTICS

Sub-items within the diagnostics menu.

SYSTEM SETUP AND EQUIPMENT TEST OPTIONS

SYSTEM SETUP (SYS SETUP1 and SYS SETUP2)

Summary of configurable system setup parameters.

EQUIPMENT TEST (EQUIP TEST)

Description of the equipment test procedure.

COOLING AND HEATING SETUP PARAMETERS

COOL SETUP

Settings for cooling airflow and fan delays.

SET COOLING RUN VALUES (CL RUN VALUES)

Adjusting compressor RPS for cooling.

HEAT SETUP

Settings for heating airflow and fan delays.