EasyManua.ls Logo

Daikin DZ9VC - Troubleshooting: Fault Codes; Fault Code Analysis (Part 3)

Daikin DZ9VC
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36

Check installation clearances.
Check the compressor; Repair/replace if needed.
Blocked/restricted condenser coil and/or lines
Faulty control board
Correct low/high line voltage condition; Contact local
Replace control board if necessary
Check the connection to thermistors; Repair/replace if
Replace control board if necessary
Check memory card data vs. air conditioner model
Replace control board if necessary
Refrigerant leak
Low refrigerant charge
Test for system leaks using leak test procedure
Check refrigerant charge level; Adjust if needed
Check circuit breakers and fuses; Replace if needed
needed
Verify unit is connected to power supply as specified on
needed
The control is unable to enter the Pump Down
thermostat. Please set thermostat to off position.
The control is unable to enter Charging Mode
thermostat. Please set thermostat to off position.
This indicates there is a voltage issue on the
troubleshooting information.
Correct low/high line voltage condition; Contact local
Replace control board if necessary
This indicates potential communication issues have
been detected by the outdoor control board.
Check the opening of stop valve, should be full open;
necessary
ClimateTalk
Fault Code
PCB LED
Display
Transmitted
ClimateTalk Message
Thermostat Fault Probable Causes Corrective Actions
(*1) Network Communication Error (Refer to “NETWORK TROUBLESHOOTING”

Related product manuals