3 | Components
Service manual
141
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
b
a
a
c
a Strip
b Compressor insulation
c Compressor
2 Route the compressor thermal protector and crankcase heater wiring out of
the compressor insulation.
3 Attach the strips.
INFORMATION
Make sure that the insulation nicely fits around the compressor.
To remove the compressor
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see "3.17Plate work"[4230].
Prerequisite: Remove the compressor insulation.
Prerequisite: Recuperate the refrigerant from the refrigerant circuit, see
"4.2.2Repair procedures"[4291].
1 If needed, remove any parts to create more space for the removal of the
compressor.
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see "To prevent
electrical hazards"[4285].
2 Remove the cover of the compressor wire terminals.