13 Disposal
Installer reference guide
87
ERGA04~08DAV3(A) + EHVH/X04+08S18+23DA
Daikin Altherma – Low temperature split
4P495248-1 – 2017.12
Error code Detailed error
code
Description
81 00 Leaving water temperature
sensor problem
89 01 Heat exchanger frozen
89 02 Heat exchanger frozen
89 03 Heat exchanger frozen
8F 00 Abnormal increase outlet water
temperature (DHW)
8H 00 Abnormal increase outlet water
temperature
8H 03 Overheating water circuit
(thermostat)
AA 01 Backup heater overheated
AA 02 External backup heater
overheated
AH 00 Tank disinfection function not
completed correctly
AJ 03 Too long DHW heat-up time
required
C0 00 Water flow detected while pump
is OFF
C0 01 Flow switch malfunction
C0 02 Flow switch malfunction
C4 00 Heat exchanger temperature
sensor problem
CJ 02 Room temperature sensor
problem
EC 00 Abnormal increase tank
temperature
EC 04 Tank preheating
H1 00 External temperature sensor
problem
HC 00 Tank temperature sensor
problem
HC 01 Second tank temperature sensor
problem
HJ 10 Water pressure sensor
abnormality
JA 17 Refrigerant pressure sensor
abnormality
U3 00 Under floor heating screed dryout
function not completed correctly
U4 00 Indoor/outdoor unit
communication problem
U5 00 User interface communication
problem
U8 01 Connection with LAN adapter lost
U8 02 Connection with room thermostat
lost
U8 03 No connection with room
thermostat
UA 00 Indoor unit, outdoor unit matching
problem
UA 17 Tank type problem
UA 21 Extension/hydro mismatch
problem
UA 22 Communication problem between
control box and option box
INFORMATION
In case of error code AH and no interruption of the
disinfection function occurred due to domestic hot water
tapping, following actions are recommended:
▪ When the Domestic hot water > Type > Reheat or
Reheat + sched. is selected, it is recommended to
program the start-up of the disinfection function at least
4 hours later than the last expected large hot water
tapping. This start-up can be set by installer settings
(disinfection function).
▪ When the Domestic hot water > Type > Scheduled only
is selected, it is recommended to program a Storage
eco 3 hours before the scheduled start-up of the
disinfection function to preheat the tank.
NOTICE
When the minimum water flow is lower than described in
the table below, the unit will temporarily stop operation and
the user interface will display error 7H‑01. After some time,
this error will reset automatically and the unit will resume
operation.
INFORMATION
Error AJ-03 is reset automatically from the moment there is
a normal tank heat-up.
INFORMATION
How an error code can be reset will be displayed on the
user interface connected on the indoor unit.
13 Disposal
NOTICE
Do NOT try to dismantle the system yourself: the
dismantling of the system, treatment of the refrigerant, oil
and other parts MUST comply with applicable legislation.
Units MUST be treated at a specialised treatment facility
for reuse, recycling and recovery.
13.1 Overview: Disposal
Typical workflow
Disposing of the system typically consists of the following stages:
1 Pumping down the system.
2 Bringing the system to a specialized treatment facility.
INFORMATION
For more details, see the service manual.
13.2 To pump down
Example: To protect the environment, pump down when relocating
the unit or when disposing of the unit.
Final English - Tanslations in progress