7
Fancoil address Destination
Address 001 Leave free!
Address 002 Kitchen
Address 003 Living room
Address 004 Bedroom 1
... ...
Do not assign any fancoil to 001. This precaution will allow
any replacements and/or additions of network devices in
the future.
Troubleshooting
Problem Cause Solution
You cannot turn the unit on with the but-
ton
The button is disabled and the program-
ming has set the status to o
Check that ag 1 of the WEB register (247)
is not active
The CP input of the board is closed
If the E_SAVING (209) register is set to 0
when the CP contact presence closes, the
PCB goes into standby mode.
Check the input status.
You cannot turn o the appliance using
the button or change function
All the keys are disabled
Check that Flag 6 of the WEB register (247)
is not active
It is not possible to increase or decrease
the temperature setting outside of set
values
The programming imposes a limit range
for adjusting the temperatures
Check that Flag 5 of the WEB register (247)
is not active and, if necessary, change the
values of the SPL_W (245) and SPH_W
(246) registers