ESIE11-02 Checking the Inputs and Outputs
Part 3 – Troubleshooting 3–19
33
4
5
1
Overview fuses and
overcurrent
The table below contains an overview of the fuses and overcurrent for types EUWA*5-24KBZW1 and
EUWY*5-24KBZW1.
All models (400 V)
Fuses +
overcurrent
5HP 8HP 10HP 12HP 16HP 20HP 24HP
F4 8 A8 A8 A8 A8 A8 A8 A
F5 125 mAT 125 mAT 125 mAT 125 mAT 125 mAT 125 mAT 125 mAT
F7, F8 5A 5A 5A 5A 5A 5A 5A
F1U 5A5A5A5A5A5A5A
F3U 315 mAT 315 mAT 315 mAT 315 mAT 315 mAT 315 mAT 315 mAT
K4S 9 A 13 A 16 A 24 A 13 A 16 A 24 A
K5S ___ ___ ___ ___ 13 A 16 A 24 A
K6S
(st. pump)
1.4 A 1.4 A 1.4 A 1.4 A 2 A 2 A 2 A
K6S
(op. pump
high)
2 A2 A2 A2 A3.7 A3.7 A3.7 A
Units with integrated pump
Fuses 5HP 8HP 10HP 12HP 16HP 20HP 24HP
F1, F2, F3
(=gL/gG)
3 X 20 A 3 X 25 A 3 X 32 A 3 X 40 A 3 X 50 A 3 X 50 A 3 X 63 A
Units without integrated pump
Fuses 5HP 8HP 10HP 12HP 16HP 20HP 24HP
F1, F2, F3
(=gL/gG)
3 X 20 A 3 X 25 A 3 X 25 A 3 X 32 A 3 X 40 A 3 X 50 A 3 X 63 A