Troubleshooting ESIE11-02
3–34 Part 3 – Troubleshooting
3
1
3
4
5
(*) Bold = different from default, “-” = not applicable because of other setting
(**) level type (L-P): D=Direct, U=User, S=Super user, F=Factory
Parameter code
Description
SW version
Default level type (L-P)
Modified level type (L-P)
Carel default value (S-P)
Unit of measurement
EUWA*5-8-10-12K* standard
EUWA*5-8-10-12K* OP ZL
EUWA*5-8-10-12K* OP ZH
EUWA*16-20-24K* standard
EUWA*16-20-24K* OP ZL
EUWA*16-20-24K* OP ZH
EUWY*5-8-10-12K* standard
EUWY*5-8-10-12K* OP ZL
EUWY*5-8-10-12K* OP ZH
EUWY*16-20-24K* standard
EUWY*16-20-24K* OP ZL
EUWY*16-20-24K* OP ZH
R/W
Supervis variable
Modbus
Type
7. Unit setting parameters
(H*)
---
H01Unit type 1,9FF2 - 222222333333R/W 54 261 INT
H02 Number of condensers 1,9 F F 0 - 000000000000R/W1212DIG
H03Number of evaporators 1,9FF0 - 000000000000R/W1313DIG
H04 Number of comp per circuit 1,9 F F 0 - 0 0 0 111000111R/W 55 262 INT
H05Pump func logic 1,9FF1 - 111111111111R/W56263INT
H06Cooling/heating pump 1,9UU0 - 000000000000R/W1414DIG
H07On/off input 1,9UU0 - 000000000000R/W1515DIG
H08Network configuration 1,9FF0 - 000000000000R/W57264INT
H09Keyboard lockup 1,9UU1 - 111111111111R/W1616DIG
H10Serial address 1,9UU1 - 111111111111R/W58265INT
H11 Output modes 1,9 F F 0 - 0 0 0 999000999R/W 59 266 INT
H12 Capacity control and
reversing valve logic
1,9 F F 1 000000000000R/W 60 267 INT
H14 1,9FF2.0- ----------------
H15 1,9FF30- ----------------
H16 1,9FF0 - 000000000000R/W2222DIG
H17 1,9FF0.0- ----------------
H18 1,9FF80- ----------------
H19 1,9FF80- ----------------
H21Second pump function 1,9FF0 - 000000000000R/W62269INT
H22Disable load default values1,9FF0 - 000000000000R/W1818DIG
H23 Enable Modbus 1,9 F U 0 - 000000000000R/W1111DIG
8. Alarm setting
parameters (P*)
---
P01 Flow start timer 1,9 U F 20sec202020202020202020202020R/W63270INT
P02 Flow stop timer 1,9 U F 5sec555555555555R/W64271INT
P03 LP bypass timer 1,9 U F 40 sec 60 60 60 60 60 60 60 60 60 60 60 60 R/W 65 272 INT
P05Alarm reset 1,9FF0 - 000000000000R/W67274INT
P06 Cooling/heating logic 1,9 F F 0 - 111111111111R/W 19 19 DIG
P08DI1 selection 1,9FF0 - 111111111111R/W69276INT
P09 DI2 selection 1,9 F U 0-999999999999R/W 70 277 INT
P13 1,9FF0- ----------------
P15 LP alarm when the compr.
is OFF
1,9FF0 - 000000000000R/W76283INT
P16 1,9 U F 80°C----------------
P17 1,9 U F 30min----------------
P19 1,9 U F 10- ----------------
P20 Enable system startup
protection
1,9 U F 0 - 000000000000R/W2020DIG
P21 Alarm relay output logic 1,9 U F 0 - 000000000000R/W88DIG
P22 1,9 U F 40sec----------------
P23 1,9 U F 40sec----------------
P25 1,9 U F 0- ----------------