Functional Control ESIE10-01
2–50 Part 2 – Functional Description
3
1
2
4
5
2.3.6 Economizer Control
The economizer shall be activated when the circuit is in a run state and the capacity exceeds 95%.
It shall turn back off when either the load drops below 60% or the circuit is no longer in a run state.
ON
60% 95%
OFF
Economizer
Compressor Capacity