ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–5
33
4
5
1
1.2.1 Phase Volts Loss/GFP Fault
Alarm description (as shown on screen): Unit PVM/GFP Fault.
Trigger: PVM set point is set to Single Point and PVM/GFP input is low.
Action Taken: Rapid stop all circuits.
Reset: Auto reset when PVM input is high or PVM set point does not equal single point for at least 5
seconds.