General Outline ESIE10-01
1–46 Part 1 – System Outline
3
11
4
5
Model EWAD~C-XS
C15C16C17C18C19
Power Supply Phase 3
Frequency Hz 50
Voltage V 400
Voltage Tolerance Minimum % -10%
Maximum % +10%
Unit Maximum starting current A 1213 1258.6 1317.8 1377 1385
Nominal running current cooling A 787 834 885 934 985
Maximum running current A 1017 1074 1146 1218 1290
Maximum current for wires sizing A 1119 1181 1261 1340 1419
Fans Nominal running current in cooling A 96 96 104 112 120
Compressor Phase No. 3
Voltage V 400
Voltage Tolerance Minimum % -10%
Maximum % +10%
Maximum running current A 390+390
+326
390+390
+390
326+326
+390
390+390
+326
390+390
+390
Starting Method Wye - Delta type (Y -Δ)