1.17 Electrical Specifications: EWAD~C-XS
Electrical
specifications
The table below contains the electrical specifications
Model EWAD~C-XS
760 830 890 990
Power Supply Phase 3
Frequency Hz 50
Voltage V 400
Voltage Tolerance Minimum % -10%
Maximum % +10%
Unit Maximum starting current A 636.4 681.2 681.2 920.2
Nominal running current cooling A 386 423 463 511
Maximum running current A 494 548 594 659
Maximum current for wires sizing A 543 603 653 725
Fans Nominal running current in cooling A 48 56 56 64
Compressor Phase No. 3
Voltage V 400
Voltage Tolerance Minimum % -10%
Maximum % +10%
Maximum running current A 223+223 223+269 269+269 269+326
Starting Method Wye - Delta type (Y -Δ)
Model EWAD~C-XS
C10 C11 C12 C13 C14
Power Supply Phase 3
Frequency Hz 50
Voltage V 400
Voltage Tolerance Minimum % -10%
Maximum % +10%
Unit Maximum starting current A 965.8 1033 1033 1033 1167.4
Nominal running current cooling A 559 608 668 686 729
Maximum running current A 716 796 860 860 960
Maximum current for wires sizing A 788 876 946 946 1056
Fans Nominal running current in cooling A 64 80 80 80 96
Compressor Phase No. 3
Voltage V 400
Voltage Tolerance Minimum % -10%
Maximum % +10%
Maximum running current A 326+326 326+390 390+390 326+326
+326
390+326
+326
Starting Method Wye - Delta type (Y -Δ)