D–EIMAC01905-23_00EN - 17/53
Fig. 7 – EWAH-TZD Gold and Platinum unit envelope
EWAD-TZD
Outside ambient air temperature
Evaporator leaving water temperature
Operation with ELWT < 4 °C requires Option 08 (brine) and glycol
Operation with ELWT > 18 °C requires Option 187 (high evaporator leaving water temperature)
Operation requires option 142 (High ambient temperature kit)
Operation at outside ambient air temperature < 5 °C requires option 229 (fan speed modulation) or option 42
(Speedroll)
The charts shown in these pages constitute a guideline on operating limits in the range.
Refer to the CSS selection software for the actual operating limits in the working conditions for each model.
Fig. 8 – EWAD-TZD Blue unit envelope