DEIMAC01905-23_00EN - 47/53
Table 20 Inverter sizes
VFD sizes
Type
90 kW
Capless
120 kW
Capless
200 kW
Capless
330 kW
Standard
400 kW
Standard
Low Ambient Start-up
Inverters include a temperature control which allows them to withstand ambient temperatures down to -20°C. However
they should not be switched on at temperatures lower than 0°C unless the following procedure is executed:
Open the switchbox (only trained technicians should perform this operation)
Open compressor fuses (by pulling the fuse holders) or compressor circuit breakers
Power on the chiller
Keep the chiller powered on for 1 hour at least (this allows inverter heaters to warm-up the inverter).
Close fuse holders
Close the switchbox